Electrical Installation

Verify Alarm Output Connections

2. Verify major output alarm functions as follows.

Enter the following command to simulate major alarm.

set alarms major on

Requirement:

Major alarm relay output contacts close (see Figure 6-16 on

page 6-29

).

Requirement:

Active Controller card Major Alarm indicator lights (Figure 6-30).

Enter the following command to turn off major alarm.

set alarms major off

Requirement:

Major alarm relay output contacts open.

Requirement:

Active Controller card Major Alarm indicator goes off.

3. Verify minor output alarm functions as follows.

Enter the following command to simulate minor alarm.

set alarms minor on

Requirement:

Minor alarm relay output contacts close (see Figure 6-16 on

page 6-29

).

Requirement:

Active Controller card Minor Alarm indicator lights (Figure 6-30).

Enter the following command to turn off minor alarm.

set alarms minor off

Requirement:

Minor alarm relay output contacts open.

Requirement:

Active Controller card Minor Alarm indicator goes off.