Carrier Access Access Navigator User Manual
Page 150
![background image](/manuals/63313/150/background.png)
6-46
August 2003
Access Navigator - Release 1.8
Electrical Installation
Verify Alarm Output Connections
2. Verify major output alarm functions as follows.
•
Enter the following command to simulate major alarm.
set alarms major on
Requirement:
Major alarm relay output contacts close (see Figure 6-16 on
).
Requirement:
Active Controller card Major Alarm indicator lights (Figure 6-30).
•
Enter the following command to turn off major alarm.
set alarms major off
Requirement:
Major alarm relay output contacts open.
Requirement:
Active Controller card Major Alarm indicator goes off.
3. Verify minor output alarm functions as follows.
•
Enter the following command to simulate minor alarm.
set alarms minor on
Requirement:
Minor alarm relay output contacts close (see Figure 6-16 on
Requirement:
Active Controller card Minor Alarm indicator lights (Figure 6-30).
•
Enter the following command to turn off minor alarm.
set alarms minor off
Requirement:
Minor alarm relay output contacts open.
Requirement:
Active Controller card Minor Alarm indicator goes off.