beautypg.com

Wire alarm input connector, Wire alarm input connector -32 – Carrier Access Access Navigator User Manual

Page 136

background image

6-32

August 2003

Access Navigator - Release 1.8

Electrical Installation

Wire Alarm Input Connector

Wire Alarm Input Connector

1. Open package containing alarm input connector.

Figure 6-19. Alarm Input Connector

2. Refer to Figure 6-20 and Figure 6-21 when wiring connector to facility alarm system.

3. Use volt-ohm meter to ensure that no voltage is present on any of the wires from the facility alarm

system (see Figure 6-21).

4. Strip the wires so that 5/16 inch of bare wire is exposed (see Figure 6-20).

5. Orient the alarm output connector as shown in Figure 6-20.

6. Insert wire into bottom opening, then tighten screw above to clamp wire in place.

7. Ensure that no bare wire shows after the wires are installed.

8. Connect cable shield to Access Navigator chassis ground or to its equipment rack. Do not ground

both ends of shield.

Figure 6-20. Alarm Input Connector Wiring

Set screws

may be on

front or top

Alarm 1

(Pins 1 & 2)

Alarm 2

(Pins 3 & 4)

Alarm 3

(Pins 5 & 6)

Strip off

insulation

5/16 inch

This wire is connected
correctly

This wire is connected
incorrectly (bare wire
is showing)

Tighten screws
to clamp wires