4 Parameter Settings and Functions

4.1.3 Limiting Torques

4-10

Using /CLT Signal

The following section describes the use of the contact output signal /CLT as a torque limit
output signal.

This signal indicates whether servomotor output torque (current) is being limited.

Settings: Pn402 (Forward Torque Limit)

Pn403 (Reverse Torque Limit)
Pn404 (Forward External Torque Limit): /P-CL input only
Pn405 (Reverse External Torque Limit): /N-CL input only

When the /CLT signal is used, the following parameter must be used to select the output sig-
nal.

Output

→ /CLT CN1-*1

Torque Limit Output

Speed/Torque
Control,
Position Control

ON Status

The circuit between CN1-
*1 and *2 is closed.
CN1-*1 is at low level.

Servomotor output torque is being limited.
(Internal torque reference is greater than the limit set-
ting.)

OFF Status

The circuit between CN1-
*1 and *2 is opened.
CN1-*1 is at high level.

Servomotor output torque is not being limited.
(Internal torque reference is less than the limit setting.)

Pn50F

Output Signal Selections 2

Factory
Setting:

0000

Speed/Torque
Control,
Position Control

+24 V

I/O power supply

Photocoupler output

Maximum operating voltage

per output: 30 VDC

Maximum operating current

per output: 50 mA DC

SERVOPACK

CN1-*1

CLT+

T-

CL

CN1-*2

Output terminal

CN1-25,26 (SO1)
CN1-27,28 (SO2)
CN1-29,30 (SO3)

/CLT

Torque limit

detection

2
3

1

Pn50F.0