4 Parameter Settings and Functions

4.3.3 Input Circuit Signal Allocation

4-54

The following parameter is used to enable input signal allocation.

In the factory setting, Pn50A.0 is set to 0. Functions in this manual are generally described for the fac-
tory settings.

„

Input Signal Allocation

The following signal can be allocated when Pn50A.0 is set to 1.

The following table shows the parameter factory settings for input signal selections 1 to 4.

Select the input terminal on the CN1 connector that will be used for each input signal.

Pn50A.0

Input Signal Allocation Mode

Factory
Setting:

0

Speed/Torque
Control,
Position Control

Pn50A.0 Setting

Description

0

Factory setting for sequence input signal allocation.
This setting is the same as Yaskawa SGDB-†AD† SERVOPACKs.

1

Enables any sequence input signal settings.

Pn50A

Input Signal Selections 1

Factory
Setting:

2100

Speed/Torque
Control,
Position Control

Pn50B

Input Signal Selections 2

Factory
Setting:

6543

Speed/Torque
Control,
Position Control

Pn50C

Input Signal Selections 3

Factory
Setting:

8888

Speed/Torque
Control,
Position Control

Pn50D

Input Signal Selections 4

Factory
Setting:

8888

Speed/Torque
Control,
Position Control

INFO

40 (SI0)
41 (SI1)
42 (SI2)
43 (SI3)
44 (SI4)
45 (SI5)
46 (SI6)

CN1

/S-ON

SERVOPACK

Determines
terminal
allocation
for input
signals.

CN1-40 is factry set for
the /S-ON input signals.

Any terminal from CN1-40 to
46 can be allocated to the
/S-ON signal through the
Pn50A.1 setting.