Page 146

4 Parameter Settings and Functions
4.5.1 Using Servo Alarm and Alarm Code Outputs
4-70
4.5 Forming a Protective Sequence
This section describes the procedure for using I/O signals from the SERVOPACK to form a pro-
tective safety sequence.
4.5.1 Using Servo Alarm and Alarm Code Outputs
The basic procedure for connecting alarm output signals is described below.
Provide an external input power supply; the SERVOPACK does not have an internal 24-V
power supply.
The use of the photocoupler output signals is described below.
These alarms are output when a SERVOPACK alarm is detected.
Photocoupler output
(per output)
Maximum operating voltage:
30 VDC
Maximum output current:
50 mA DC
Open collector output
(per output)
Maximum operating voltage:
30 VDC
Maximum output current:
20 mA DC
50 mA max.
20 mA max.
SERVOPACK
Photocoupler
I/O power supply
Host controller
CN1-31
CN1-32
ALM+
ALM-
+24 V
0 V
CN1-37
CN1-38
CN1-39
ALO1
ALO2
ALO3
SG
CN1-1
0 V
0 V
Output
→ ALM+ CN1-31
Servo Alarm Output
Speed/Torque
Control,
Position Control
Output
→ ALM- CN1-32
Signal Ground for Servo Alarm
Output
Speed/Torque
Control,
Position Control
Turns power OFF.
Alarm
detection
SERVOPACK
ALM output