6 Using the Digital Operator

6.1.5 Status Display Mode

6-8

Position Control Mode

The following tables list bit data items, codes, and their meanings.

Table 6.3 Bit Data and Meanings in Position Control Mode

Bit Data

Meaning

Control Power ON

Lit when SERVOPACK control power is ON.

Baseblock

Lit for baseblock. Not lit when servo is ON.

Positioning
Completed

Lit if error between position reference and actual motor position is below
preset value.
Not lit if error between position reference and actual motor position
exceeds preset value.
Preset value: Set in Pn500 (7 pulses are standard setting)

/TGON

Lit if motor speed exceeds preset value.
Not lit if motor speed is below preset value.
Preset value: Set in Pn502 (20 min

-1

is standard setting)

Reference Pulse
Input

Lit if reference pulse is input.
Not lit if no reference pulse is input.

Error Counter Clear
Input

Lit when error counter clear signal is input.
Not lit when error counter clear signal is not input.

Power Ready

Lit when main power supply circuit is normal.
Not lit when power is OFF.

Table 6.4 Codes and Meanings in Position Control Mode

Code

Meaning

Baseblock

Servo OFF (motor power OFF)

Run

Servo ON (motor power ON)

Forward Run Prohibited

CN1-42 (P-OT) is OFF. Refer to 4.1.2 Setting the Overtravel Limit Func-
tion
.

Reverse Run Prohibited

CN1-43 (N-OT) is OFF. Refer to 4.1.2 Setting the Overtravel Limit Func-
tion
.

Alarm Status

Displays the alarm number. Refer to 8.2 Troubleshooting.

Code

Bit data

Positioning completed

Baseblock

Control power ON

Reference pulse input

TGON
Power ready

Error counter clear input

: