Manual Zero Adjustment of Analog Monitor Output
Follow the procedure below to execute the manual zero adjustment of analog monitor out-
put.
Using the Hand-held Digital Operator
1. Press the DSPL/SET Key to select the auxiliary function mode.
2. Select the parameter Fn00C. Press the Left or Right Cursor Key to select the digit. Press
the Up or Down Cursor Key to change the number.
3. Press the DATA/ENTER Key. The following display will appear.
4. Press the DSPL/SET Key, and the monitor output for the two channels will be displayed
alternately as shown below.
5. Press the Left or Right Cursor Key to display the analog monitor output data. Pressing
the Left or Right Cursor Key again will return to the display shown in the above step 3.
or 4.
6. Press the Up or Down Cursor Key to perform zero adjustment of the analog monitor
output.
7. When zero adjustment has been completed for the two channels, press the DATA/
ENTER Key to return to the auxiliary function mode display.
DSPL/SET Key
Displayed
alternately
Data Display
Left Cursor Key
(Right Cursor Key)
Displayed
alternately
Data Display
Data Setting Change