4.1 Settings According to Device Characteristics

4-9

4

4.1.3 Limiting Torques

The SGDH SERVOPACK limits torques as follows:

• Level 1: Limits maximum output torque to protect the equipment or workpiece. (Internal

Torque Limit)

• Level 2: Limits torque after the servomotor moves the equipment to a specified position.

(External Torque Limit)

• Level 3: Always limits output torque rather than speed.
• Level 4: Switches between speed and torque limit.

Application of levels 1 and 2 in the torque limit function are described below.

„

Setting Level 1: Internal Torque Limits

Maximum torque is limited to the values set in the following parameters.

This parameter sets the maximum torque limits for forward and reverse rotation.

Use this parameter when torque must be limited due to equipment conditions.

The torque limit function always monitors torque and outputs the signals below when
the limit is reached.

The following signals are output by the torque limit function.

The torque limit is specified as a percentage of rated torque.

If torque limit is set higher than the maximum torque of the servomotor, the maximum torque of the
servomotor is the limit.

Application Example: Equipment Protection

Pn402

Forward Torque Limit

Unit:

%

Setting

Range:

0 to 800

Factory

Setting:

800

Speed/Torque
Control,
Position Control

Pn403

Reverse Torque Limit

Unit:

%

Setting

Range:

0 to 800

Factory

Setting:

800

Speed/Torque
Control,
Position Control

• /CLT
• Monitor Mode Un006

Condition that outputs a /CLT signal:

Pn50F.0 allocates an output terminal from SO1 to
SO3.

INFO

Motor
speed

Torque limit

Torque

Too small a torque limit will result in a
insufficient torque during acceleration and
deceleration.