4.2 Settings According to Host Controller
4-49
4
Confirm the allocation of input signals when using this function. (Refer to 4.3.3 Input Cir-
cuit Signal Allocation.) Factory settings are given in the following table.
Setting
The torque limit input gain is set at parameter Pn400.
The factory setting at Pn400 is 30. If, for example, the torque limit is ±3 V, then torque is
limited to 100% of the rated torque. (A torque value higher than 100% torque is clamped at
100%. A 100% torque will also be used as the limit if the input torque limit value is -3 V.)
The settings of the following parameters are also valid. The torque limit will be either the
torque limit value for the analog voltage reference or the setting of Pn404/Pn405, whichever
is smaller.
/P-CL
CN1-45 at low level when
ON
Forward torque limit
applied.
Limit: Pn404 or T-REF
input, whichever is smaller.
CN1-45 at high level when
OFF
Forward torque limit not
applied. Normal operation.
-
/N-CL
CN1-46 at low level when
ON
Reverse torque limit
applied.
Limit: Pn405 or T-REF
input, whichever is smaller.
CN1-46 at high level when
OFF
Reverse torque limit not
applied. Normal operation.
-
Pn400
Torque Reference
Input Gain
Unit:
0.1 V/rated
torque
Setting
Range:
10 to 100
Factory
Setting:
30
Speed/Torque
Control,
Position Control
Pn404
Forward External Torque
Limit
Unit:
%
Setting
Range:
0 to 800
Factory
Setting:
100
Speed/Torque
Control,
Position Control
Pn405
Reverse External Torque
Limit
Unit:
%
Setting
Range:
0 to 800
Factory
Setting:
100
Speed/Torque
Control,
Position Control