Installation, Servopack orientation, Cooling – Yaskawa Large Capacity Sigma II Series User Manual
Page 39: Side-by-side installation, Environmental conditions in the control panel

2 Basic Operation
2.2.4 Installing the SERVOPACK
2-12
Installation
Follow the procedure below to install multiple SERVOPACKs side by side in a control
panel.
SERVOPACK Orientation
Install the SERVOPACK perpendicular to the wall so the front panel containing connectors
faces outward.
Cooling
As shown in the figure above, allow sufficient space around each SERVOPACK for cooling
by cooling fans or natural convection.
Side-by-side Installation
When installing SERVOPACKs side by side as shown above, allow at least 10mm (0.39 in)
between and at least 50mm (1.97 in) above and below each SERVOPACK. Install cooling
fans above the SERVOPACKs to avoid excessive temperature rise and to maintain even tem-
perature inside the control panel.
Environmental Conditions in the Control Panel
• Ambient Temperature: 0 to 55
°C
• Humidity: 90% RH or less
• Vibration: 4.9 m/s
2
• Condensation and Freezing: None
• Ambient Temperature for Long-term Reliability: 45
°C max.
Fan
30 mm or more
10 mm or more
50 mm
or more
50 mm
or more
Fan
WARNING
5
electric shock.
Disconnect all power
May cause
before servicing.
and wait 5 min.
grounding techniques.
Use proper
WARNING
5
electric shock.
Disconnect all power
May cause
before servicing.
and wait 5 min.
grounding techniques.
Use proper
WARNING
5
electric shock.
Disconnect all power
May cause
before servicing.
and wait 5 min.
grounding techniques.
Use proper
WARNING
5
electric shock.
Disconnect all power
May cause
before servicing.
and wait 5 min.
grounding techniques.
Use proper