8 Inspection, Maintenance, and Troubleshooting

8.2.1 Troubleshooting Problems with Alarm Displays

8-32

„

A.F1

A.F1: Power Line Open Phase

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

ON

OFF

OFF

Cause

Remedy

A

One phase (L1, L2, or L3) of the main cir-
cuit power supply is disconnected.

• Check power supply.
• Check wiring of the main circuit power

supply.

• Check QF, noise filter, magnetic contac-

tor.

B

There is one phase where the line voltage is
low.

Check power supply.

C

SERVOPACK defective.

Replace SERVOPACK.

Occurred when the control
power turned ON.

C

At main circuit power
supply ON.

A, B