3.1 Two-step Trial Operation
3-7
3
Operating Procedure in Speed Control Mode: Set Pn000.1 to 0
Standard speed control setting is described here.
1. Gradually increase the reference speed input (V-REF, CN1-5) voltage. The servomotor
will rotate.
2. Check the following items in Monitor Mode. See 6.1.7 Operation in Monitor Mode.
• Has the reference speed been input?
• Is the motor speed as designed?
• Does the reference speed coincide the actual motor speed?
• Does the servomotor stop when the speed reference is 0?
3. If the servomotor rotates at extremely slow speed with 0 V specified for the reference
voltage, correct the reference offset value as described in 6.2.3 Automatic Adjustment of
the Speed and Torque Reference Offset or 6.2.4 Manual Adjustment of the Speed and
Torque Reference Offset.
4. Reset the parameters shown below to change the motor speed or direction of rotation.
Un000
Actual motor speed
Un001
Reference speed
Pn300
Speed Reference Input Gain
See 4.2.1 Speed Reference.
Pn000.0
Rotation Direction Selection
See 4.1.1 Switching Servomotor Rotation
Direction.
SERVOPACK
Reference
voltage
Servomotor
Servomotor rotates
at a speed proportional
to the reference voltage.
(CN1-5)
(CN1-6)
V-REF
SG
M