4.8.2 Wiring for Noise Control

„

Wiring Example

This SERVOPACK uses high-speed switching elements in the main circuit. It may receive
“switching noise” from these high-speed switching elements if wiring or grounding around
the SERVOPACK is not appropriate. To prevent this, always wire and ground the SERVO-
PACK correctly.

This SERVOPACK has a built-in microprocessor (CPU), so it is necessary to protect it from
external noise as much as possible by installing a noise filter in the appropriate place.

The following is an example of wiring for noise control.

* 1. For ground wires connected to the casing, use a thick wire with a thick-

ness of at least 3.5 mm

2

(0.005 in

2

) (preferably, plain stitch cooper

wire).

* 2. For wires indicated by

use twisted-pair wires whenever possible.

* 3. When using a noise filter, follow the precautions in „ Using Noise Fil-

ters (page 4-102).

SERVOPACK

SGDH

Servomotor

Wires of 3.5mm
(0.005 in ) or more

2

2

*1

(Casing)

(Casing)

(Casing)

(Casing)

(Ground plate)

Ground: Ground to an independent ground
(100

Ω max.)

z

Operation relay
sequence

z

Signal generation
circuit (provided
by user)

(Ground)

*1

(Casing)

380 to
480 VAC

Noise filter

*3

2

2

2.0 mm (0.003 in ) min.

2

2

3.5 mm
(0.005 in )
min.

2

2

2.0 mm
(0.003 in )
min.

2

2

*1

2

2

M

(FG)

U

W

V

L2

L1

L3

CN2

1LF

AVR

*2

2LF

PG

*3

0V

+

-

24 VDC

DC24P

DC24N

380 to 480 V

3.5 mm (0.005 in ) min.

3.5 mm
(0.005 in )
min.