8.2 Troubleshooting

8-17

8

„

A.7A

A.7A: Heat Sink Overheated

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

ON

ON

ON

OFF

Cause

Remedy

A

The ambient temperature of the SERVO-
PACK exceeded 55

°C.

Alter conditions so that the ambient temper-
ature goes below 55

°C.

B

The air flow around the heat sink is bad.

Follow the installation method and provide
sufficient space as specified.

C

Fan stopped.

Replace SERVOPACK.

D

SERVOPACK is operating under an over-
load.

Reduce load.

E

SERVOPACK defective.

Replace SERVOPACK.

When control power turned
ON

E

During servomotor
operation

A, B,
C, D