8 Inspection, Maintenance, and Troubleshooting

8.2.1 Troubleshooting Problems with Alarm Displays

8-30

„

A.d0

A.d0: Position Error Pulse Overflow

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

ON

ON

OFF

OFF

Cause

Remedy

A

Servomotor wiring incorrect.

Check and correct wiring.

B

SERVOPACK was not correctly adjusted.

Increase speed loop gain (Pn100) and posi-
tion loop gain (Pn102).

C

Motor load was excessive.

Reduce load torque and moment of inertia.
Otherwise, replace with larger capacity ser-
vomotor.

D

Position reference pulse frequency was too
high.

• Increase or decrease reference pulse fre-

quency.

• Add smoothing function.
• Correct electronic gear ratio.

E

Circuit board (1PWB) defective.

Replace SERVOPACK.

At power ON

E

During servomotor
operation

Overflow occurs during
high speed rotation

A

Reference pulse is input
properly, but feedback
pulse is not returned.

E

Operation is normal,but
overflow occurs when
long reference is input.

B, C, D