5.2 High-speed Positioning

5-7

5

The above parameters are automatically set by the autotuning operation.

„

Setting Position Loop Gain

Set the following position loop-related parameter as required.

The above constant is the position loop gain for the SERVOPACK.

The higher the position loop gain, the smaller the position control error will be. There is,
however, a certain limit depending on machine characteristics.

This gain setting is also valid for zero clamp operation.

The above parameter is automatically set by the autotuning operation.

Set in this parameter the error pulse level at which a position error pulse overflow alarm
(A.d0) is detected.

If the machine permits only a small position loop gain value to be set in Pn102, an overflow
alarm may arise during high-speed operation. In this case, increase the value set in this
parameter to suppress alarm detection.

Pn102

Position Loop Gain (Kp)

Unit:

1/s

Setting

Range:

1 to 2000

Factory

Setting:

40

Speed Control,
Position Control

Pn505

Overflow level

Unit:

256 ref-

erence

units

Setting

Range:

1 to 32767

Factory

Setting:

1024

Position Control

Position reference

Position loop gain

Position feedback

+

-

Kp

Error pulse

0

-

+

ìPn505î

Alarm (A.d0)

Normal control

Alarm (A.d0)