4 Parameter Settings and Functions

4.2.12 Reference Pulse Inhibit Function (INHIBIT)

4-50

4.2.12 Reference Pulse Inhibit Function (INHIBIT)

This function inhibits the SERVOPACK from counting input reference pulses during posi-
tion control.

The servomotor remains locked (clamped) while the function is in use. The /P-CON (/
INHIBIT) signal is used to enable or disable the function.

„

Using Reference Pulse Inhibit Function (INHIBIT)

To use the inhibit function, set the parameter as shown below.

The following settings enable the inhibit function.

Note: Parentheses () around an /INHIBIT signal indicate that a signal has

been allocated to the input circuit. See 4.3.3 Input Circuit Signal Allo-
cation
.

Pn000.1

Control Method Selection

Factory

Setting:

0

Position Control

Pn000.1 Setting

Description

1

Disables the inhibit function.
Always counts reference pulses.

B

Enables the inhibit function. The /P-CON (/INHIBIT) signal is used to
enable or disable the inhibit function.

/P-CON (/INHIBIT)

Description

OFF

Counts reference pulses.

ON

Prohibits the SERVOPACK from counting refer-
ence pulses.
The servomotor remains locked.

Error
counter

Feedback pulse

Reference
pulse

SERVOPACK

Pn000.1

1

B

OFF

ON

+

-

/P-CON (/INHIBIT)

/P-CON

(/INHIBIT)