4.2.12 Reference Pulse Inhibit Function (INHIBIT)
4-50
4.2.12 Reference Pulse Inhibit Function (INHIBIT)
This function inhibits the SERVOPACK from counting input reference pulses during posi-
tion control.
The servomotor remains locked (clamped) while the function is in use. The /P-CON (/
INHIBIT) signal is used to enable or disable the function.
Using Reference Pulse Inhibit Function (INHIBIT)
To use the inhibit function, set the parameter as shown below.
The following settings enable the inhibit function.
Note: Parentheses () around an /INHIBIT signal indicate that a signal has
been allocated to the input circuit. See 4.3.3 Input Circuit Signal Allo-
cation.
Pn000.1
Control Method Selection
Factory
Setting:
0
Position Control
Pn000.1 Setting
Description
1
Disables the inhibit function.
Always counts reference pulses.
B
Enables the inhibit function. The /P-CON (/INHIBIT) signal is used to
enable or disable the inhibit function.
/P-CON (/INHIBIT)
Description
OFF
Counts reference pulses.
ON
Prohibits the SERVOPACK from counting refer-
ence pulses.
The servomotor remains locked.
Error
counter
Feedback pulse
Reference
pulse
SERVOPACK
Pn000.1
1
B
OFF
ON
+
-
/P-CON (/INHIBIT)
/P-CON
(/INHIBIT)