A.10, Display and outputs, Status and remedy for alarm – Yaskawa Large Capacity Sigma II Series User Manual
Page 347

8 Inspection, Maintenance, and Troubleshooting
8.2.1 Troubleshooting Problems with Alarm Displays
8-8
A.10
A.10: Overcurrent or Heat Sink Overheated
Display and Outputs
Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is
ON.
Status and Remedy for Alarm
Note: E to H can occur with a SERVOPACK with a capacity of all models
(400 V) and 1.5 kW to 5 kW (200 V).
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
OFF
OFF
OFF
Cause
Remedy
A
Wiring shorted between SERVOPACK and
servomotor.
Check and correct wiring.
B
Servomotor phase U, V, or W shorted.
Replace the servomotor.
C
• Circuit board (1PWB) defective.
• Power transistor defective.
Replace SERVOPACK.
D
Current feedback circuit, power transistor,
DB circuit, or circuit board defective.
Replace SERVOPACK.
E
The ambient temperature of the SERVO-
PACK exceeded 55
°C.
Alter conditions so that the ambient temper-
ature goes below 55
°C.
F
The air flow around the heat sink is bad.
Follow the installation method and provide
sufficient space as specified.
G
Fan stopped.
Replace SERVOPACK.
H
SERVOPACK is operating under an over-
load.
Reduce load.
A, B, D, E,
F, G, H
C, D
C
During servomotor
operation
When SERVO ON (/S-ON)
signal turned ON
At power ON