8 Inspection, Maintenance, and Troubleshooting

8.2.1 Troubleshooting Problems with Alarm Displays

8-8

„

A.10

A.10: Overcurrent or Heat Sink Overheated

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Note: E to H can occur with a SERVOPACK with a capacity of all models

(400 V) and 1.5 kW to 5 kW (200 V).

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

ON

OFF

OFF

OFF

Cause

Remedy

A

Wiring shorted between SERVOPACK and
servomotor.

Check and correct wiring.

B

Servomotor phase U, V, or W shorted.

Replace the servomotor.

C

• Circuit board (1PWB) defective.
• Power transistor defective.

Replace SERVOPACK.

D

Current feedback circuit, power transistor,
DB circuit, or circuit board defective.

Replace SERVOPACK.

E

The ambient temperature of the SERVO-
PACK exceeded 55

°C.

Alter conditions so that the ambient temper-
ature goes below 55

°C.

F

The air flow around the heat sink is bad.

Follow the installation method and provide
sufficient space as specified.

G

Fan stopped.

Replace SERVOPACK.

H

SERVOPACK is operating under an over-
load.

Reduce load.

A, B, D, E,
F, G, H

C, D

C

During servomotor
operation

When SERVO ON (/S-ON)
signal turned ON

At power ON