Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 99
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
99
Protective Trip and Warning Functions Chapter 5
Jam Trip
The E300 Electronic Overload Relay will trip with a jam indication if:
•
No trip currently exists
•
Jam Trip is enabled
•
Jam Inhibit Time has expired
•
The maximum phase current is greater than the Jam Trip Level for a time
period greater than the Jam Trip Delay.
If the E300 Electronic Overload Relay trips on a jam, the:
•
TRIP/WARN LED status indicator will flash a red 5-short blink pattern
•
Bit 4 in Current Trip Status (Parameter 4) will set to 1
•
Bit 0 in Device Status 0 (Parameter 20) will set to 1
•
Any relay outputs configured as a Trip Relay will open
•
Any relay outputs configured as a Control Relay will open
•
Any relay outputs configured as a Trip Alarm will close
•
Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)
Jam Trip Delay
Jam Trip Delay (Parameter 252) allows the installer to define the time period a
jam condition must be present before a trip occurs. It is adjustable from
0.1…25.0 s.
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT00 Protection Fault Action (Parameter 304)
• Output PT00 Protection Fault Value (Parameter 305)
• Output PT01 Protection Fault Action (Parameter 310)
• Output PT01 Protection Fault Value (Parameter 311)
• Output PT02 Protection Fault Action (Parameter 316)
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)