Chapter 7, Metering and diagnostics, Introduction – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 219: Device monitor, Percent thermal capacity utilized, Introduction device monitor, Chapter
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
219
Chapter
7
Metering and Diagnostics
Introduction
The purpose of this chapter is to provide detailed information regarding the
metering and diagnostic information that the E300 Electronic Overload Relay
generates. The metering and diagnostic functions are organized into seven
sections:
•
Device Monitor
•
Current Monitor
•
Voltage Monitor
•
Power Monitor
•
Energy Monitor
•
Trip/Warning History
•
Trip Snapshot
Device Monitor
The E300 Electronic Overload Relay's device monitor diagnostics provides
information on the status of the E300 Electronic Overload Relay which includes:
•
Thermal overload protection
•
Trip and warning protection functions
•
Digital inputs and relay outputs
•
Operator station
•
Hardware options
•
Time and date
Percent Thermal Capacity Utilized
Percent Thermal Capacity Utilized (Parameter 1) reports the calculated percent
thermal capacity utilization of the motor being monitored. When the percent
thermal capacity utilization equals 100%, the E300 Electronic Overload Relay
will issue an overload trip.