External line current transformer application, Current transformer ratio – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 44

background image

44

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 2 Installation and Wiring

Figure 33 - E300 DOL and Single-Phase Full Voltage Connections

External Line Current
Transformer Application

Current Transformer Ratio

The following E300 Electronic Overload Relay sensing module catalog numbers
can be used with step down current transformers:

193-ESM-IG-30A-E3T

193-ESM-IG-30A-T

193-ESM-IG-30A-P

193-ESM-I-30A-E3T

193-ESM-I-30A-T

193-ESM-I-30A-P

193-ESM-VIG-30A-CT

CT Primary (Parameter 263) and CT Secondary (Parameter 264) allows the user
to identify the turns ratio of the step down current transformers in use. The E300
Electronic Overload Relay will automatically adjust the measured current based
on these two configuration parameters. Users will use the primary current for
their FLA settings.

Table 13 - CT Primary (Parameter 263)

L 1

2/T1

4/T2

6/T3

M

T1

Three-Phase Direct-On-Line

Single-Phase Full-Voltage

T2

L 2

E300

L 1

2/T1

4/T2

6/T3

M

T1

T2

T3

S.C.P.D.

L 2

L 3

S.C.P.D.

E300

CT Primary (Parameter 263)

Default Value

5

Minimum Value

1

Maximum Value

65535