beautypg.com

L2-l3 voltage, Average l-l voltage, L2-l3 voltage average l-l voltage – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 243

background image

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

243

Metering and Diagnostics Chapter 7

L2-L3 Voltage

L2-L3 Voltage (Parameter 54) reports the voltage in volts in reference to the T2
and T3 power terminals of the E300 Electronic Overload Relay Sensing Module.

Table 257 - L2-L3 Voltage (Parameter 54)

Table 258 - L3-L1 Voltage

L3-L1 Voltage (Parameter 55) reports the voltage in volts in reference to the T3
and T1 power terminals of the E300 Electronic Overload Relay Sensing Module.

Table 259 - L3-L1 Voltage (Parameter 55)

Average L-L Voltage

Average L-L Voltage (Parameter 56) reports the average voltage of the monitored
L-L voltages. When Single or Three Phase (Parameter 176) is set to

Three Phase,

Average L-L Voltage is calculated as follows:

Average L-L Voltage = (L1-L2 Voltage + L2-L3 Voltage + L3-L1 Voltage) / 3

When Single or Three Phase (Parameter 176) is set to

Single Phase, Average L-L

Voltage is calculated as follows:

Average L-L Voltage = (L1-L2 Voltage + L2-L3 Voltage) / 2

Table 260 - Average L-L Voltage (Parameter 56)

Default Value

0.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

Volts

Default Value

0.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

10

Units

Volts

Default Value

0.0

Minimum Value

0.0

Maximum Value

6553.5

Parameter Type

UINT

This manual is related to the following products: