L2-l3 voltage, Average l-l voltage, L2-l3 voltage average l-l voltage – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 243

Rockwell Automation Publication 193-UM015B-EN-P - June 2014
243
Metering and Diagnostics Chapter 7
L2-L3 Voltage
L2-L3 Voltage (Parameter 54) reports the voltage in volts in reference to the T2
and T3 power terminals of the E300 Electronic Overload Relay Sensing Module.
Table 257 - L2-L3 Voltage (Parameter 54)
Table 258 - L3-L1 Voltage
L3-L1 Voltage (Parameter 55) reports the voltage in volts in reference to the T3
and T1 power terminals of the E300 Electronic Overload Relay Sensing Module.
Table 259 - L3-L1 Voltage (Parameter 55)
Average L-L Voltage
Average L-L Voltage (Parameter 56) reports the average voltage of the monitored
L-L voltages. When Single or Three Phase (Parameter 176) is set to
Three Phase,
Average L-L Voltage is calculated as follows:
Average L-L Voltage = (L1-L2 Voltage + L2-L3 Voltage + L3-L1 Voltage) / 3
When Single or Three Phase (Parameter 176) is set to
Single Phase, Average L-L
Voltage is calculated as follows:
Average L-L Voltage = (L1-L2 Voltage + L2-L3 Voltage) / 2
Table 260 - Average L-L Voltage (Parameter 56)
Default Value
0.0
Minimum Value
0.0
Maximum Value
6553.5
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
Volts
Default Value
0.0
Minimum Value
0.0
Maximum Value
6553.5
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
10
Units
Volts
Default Value
0.0
Minimum Value
0.0
Maximum Value
6553.5
Parameter Type
UINT