beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 39

background image

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

39

Installation and Wiring Chapter 2

Table 4 - E300 Expansion Analog Module Wire Size and Torque Specifications

Figure 30 - E300 Expansion Analog I/O Modules 193-EXP-AIO-__

Wire Type

Conductor Torque

Cat. No.
193-EXP-AIO-31

Stranded/Solid [AWG]

Single

24...12 AWG

Multiple
(stranded only)

24...16 AWG
5 lb-in

Flexible-Stranded with Ferrule Metric

Single

0.25…2.5 mm

2

Multiple

0.5...0.75 mm

2

0.55 N•m

Coarse-Stranded/Solid Metric

Single

0.2...2.5 mm

2

Multiple

0.2...1.5 mm

2

0.55 N•m

Analog Current Input

Analog Voltage Input

24V DC

Power

Supply

INx+

INx-

+

-

Current

Input

Device

INx+

-V

+V

INx-

Analog Voltage or Current Output

+

Out-

Out+

Device
-

2 Wire RTD

INx+

INx-

INx-

3 Wire RTD

INx+

RSx

This manual is related to the following products: