Environmental specifications – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 325
![background image](/manuals/577641/325/background.png)
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
325
Specifications Appendix A
Environmental Specifications
➊ Current ratings must be derated at altitudes greater than 2000 m
➋ Temperature rating based on 120V AC control module with 1 A going through relays 0, 1, and 2.
➌ Temperature rating based on 240V DC control module with four digital inputs active and 0.2 A going through
relays 0, 1, and 2.
➍ Temperature rating based on 120V AC or 240V AC control module with 5A going through relays 0, 1, and 2.
NOTE:
The E300 Electronic Overload Relay expansion power supplies (Cat.
Nos. 193-EXP-PS-AC and 193-EXP-PS-DC) surrounding air temperature must
not exceed 55 °C (131 °F).
Table 348 - Expansion Digital I/O Modules
Expansion Digital I/O Modules
193-EXP-DIO-42-24D 193-EXP-DIO-42-120 193-EXP-DIO-42-240
Digital Output Rated Operational Voltage (U
e
):
250V AC
250V AC
250V AC
Digital Output Rated Insulation Voltage (U
i
):
2000Vrms for 1s
2000Vrms for 1s
2000Vrms for 1s
Rated Impulse Withstand Voltage (U
imp
):
NA
NA
NA
Conditional Short Circuit Current:
1000 A
1000 A
1000 A
Recommended Control Circuit Fuse:
KTK-R (6 A, 600V)
KTK-R (6 A, 600V)
KTK-R (6 A, 600V)
Utilization Category:
AC15, DC13
AC15, DC13
AC15, DC13
Pollution Degree:
3
3
3
Table 349 - Expansion Power Supply Modules
Expansion Power Supply Modules
193-EXP-PS-AC
Rated Operational Voltage (U
e
):
100…250V AC
Rated Insulation Voltage (U
i
):
2640Vrms for 1s
Rated Impulse Withstand Voltage (U
imp
):
4 kV
Conditional Short Circuit Current:
NA
Protection Against Short Circuits:
NA
Utilization Category:
NA
Pollution Degree:
3
Table 350 - Environmental Specifications
Ambient Temperature
Storage
Operating
(Open)
(Enclosed)
–40…+85
C (–40…+185 F)
–20…+55
C (–4…+131 F)➋➌
–20…+40
C (–4…+104 F)➌➍
Humidity
Operating
Damp Heat – Steady State (per IEC 68-2-3)
Damp Heat – Cyclic (per IEC 68-2-30)
5…95% Non-condensing
92% r.h., 40
C (104 F), 56 days
93% r.h., 25
C/40 C (77 F/104 F), 21 Cycles
Cooling Method
Natural Convection
Vibration (per IEC 68-2-6)
2.5G operating, 5 G non-operating
Shock (per IEC 68-2-27)
30 G
Maximum Altitude
2000 m
➊
Pollution Environment
Pollution Degree 3
Terminal Marking
EN 50012
Degree of Protection
IP20