Warning history mask, Current warning history mask, Voltage warning history mask – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 273
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
273
Metering and Diagnostics Chapter 7
Warning History Mask
Users can decide which warning events are recorded into the E300 Electronic
Overload Relay’s warning history by using the Warning History Masks.
Current Warning History Mask
Current Warning History Mask (Parameter 145) allows users to select which
current based warning events are recorded in the warning history.
Table 322 - Current Warning History Mask (Parameter 145)
Voltage Warning History Mask
Voltage Warning History Mask (Parameter 146) allows users to select which
voltage based warning events are recorded in the warning history.
88
Analog Expansion Module 4 is not operating properly
90
Control Module installed does not match the expected type
91
Sensing Module installed does not match the expected type
92
Comms Module installed does not match the expected type
93
Operator Station installed does not match expected type
94
Digital Module installed does not match the expected type
95
Analog Module installed does not match the expected type
98
A hardware fault condition was detected
Warning History Code Description
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Overload Warning
Reserved
X
Ground Fault Warning
Reserved
X
Jam Warning
X
Underload Warning
X
Current Imbalance Warning
X
L1 Under Current Trip
X
L2 Under Current Trip
X
L3 Under Current Trip
X
L1 Over Current Trip
X
L2 Over Current Trip
X
L3 Over Current Trip
X
L1 Line Loss Trip
X
L2 Line Loss Trip
X
L3 Line Loss Trip