Sensing module type (parameter 222), Communication module type (parameter 223) – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 57
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
57
System Operation and Configuration Chapter 3
Sensing Module Type (Parameter 222)
The E300 Electronic Overload Relay offers 12 different sensing modules. Place
the value of the expected sensing module into Parameter 222. A value of (0)
disables the Option Match feature for the sensing module.
Table 26 - Sensing Module Type (Parameter 222)
Communication Module Type (Parameter 223)
The E300 Electronic Overload Relay offers two different communication
modules. Place the value of the expected communication module into Parameter
223. A value of (0) disables the Option Match feature for the communication
module.
Table 27 - Communication Module Type (Parameter 223)
Code
Description
Sensing Module Cat. No.
0
Ignore
—
1
Voltage / Current 0.5…30 A / Ground Fault
193-ESM-VIG-30A-__ or 592-ESM-VIG-30A-__
2
Voltage / Current 6…60 A / Ground Fault
193-ESM-VIG-60A-__ or 592-ESM-VIG-60A-__
3
Voltage / Current 10…100 A / Ground Fault
193-ESM-VIG-100A-__ or 592-ESM-VIG-100A-__
4
Voltage / Current 20…200 A / Ground Fault
193-ESM-VIG-200A-__ or 592-ESM-VIG-200A-__
5
Current 0.5…30 A / Ground Fault
193-ESM-IG-30A-__ or 592-ESM-IG-30A-__
6
Current 6…60 A / Ground Fault
193-ESM-IG-60A-__ or 592-ESM-IG-60A-__
7
Current 10…100 A / Ground Fault
193-ESM-IG-100A-__ or 592-ESM-IG-100A-__
8
Current 20…200 A / Ground Fault
193-ESM-IG-200A-__ or 592-ESM-IG-200A-__
9
Current 0.5…30 A
193-ESM-I-30A-__ or 592--ESM-I-30A-__
10
Current 6…60 A
193-ESM-I-60A-__ or 592--ESM-I-60A-__
11
Current 10…100 A
193-ESM-I-100A-__ or 592--ESM-I-100A-__
12
Current 20…200 A
193-ESM-I-200A-__ or 592--ESM-I-200A-__
Code
Description
Communication Module Cat. No.
0
Ignore
—
1
EtherNet/IP with Dual Port Switch supporting DLR
193-ECM-ETR
2
DeviceNet
193-ECM-DNT