274
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 7 Metering and Diagnostics
Table 323 - Voltage Warning History Mask (Parameter 146)
Power Warning History Mask
Power Warning History Mask (Parameter 147) allows users to select which
power based warning events are recorded in the warning history.
Table 324 - Power Warning History Mask (Parameter 147)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Under Voltage Warning
X
Over Voltage Warning
X
Voltage Imbalance Warning
X
Phase Rotation Warning
X
Under Frequency Warning
X
Over Frequency Warning
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Under kW Warning
X
Over kW Warning
X
Under kVAR Consumed Warning
X
Over kVAR Consumed Warning
X
Under kVAR Generated Warning
X
Over kVAR Generated Warning
X
Under kVA Warning
X
Over kVA Warning
X
Under Power Factor Lagging Warning
X
Over Power Factor Lagging Warning
X
Under Power Factor Leading Warning
X
Over Power Factor Leading Warning
Reserved
Reserved
Reserved
Reserved