Control supervisor object — class code 0x0029 – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 400

background image

400

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Appendix C EtherNet/IP Information

Table 405 - Discrete Output Group Object Instance 1 Attributes

Instances 2-5 each represent a single expansion module. They have the following
attributes.

Table 406 - Discrete Output Group Object Instance 2…5 Attributes

The following common services are implemented for the Discrete Output Group
Object.

Table 407 - Discrete Output Group Object Common Services

Control Supervisor Object — CLASS CODE 0x0029

No class attributes are supported.

A single instance (instance 1) of the Control Supervisor Object is supported.

Attribute ID Access Rule

Name

Data Type

Value

3

Get

Number of Instances

USINT

11

4

Get

Binding

Array of UINT

1,2,3,4,5,6,7,8,9,10,11

6

Get/Set

Command

BOOL

0=idle; 1=run

104

Get/Set

Network Status
Override

BOOL

0=No Override (go to safe state)
1=Override (run local logic)

105

Get/Set

Comm Status Override BOOL

0=No override (go to safe state)
1=Override (run local logic)

Attribute ID Access Rule

Name

Data Type

Value

3

Get

Number of Instances

USINT

2

4

Get

Binding

Array of UINT

Instance 2: 4, 5
Instance 3: 6, 7
Instance 4: 8, 9
Instance 5: 10, 11

6

Get/Set

Command

BOOL

0=idle; 1=run

7

Get/Set

Fault Action

BOOL

0=Fault Value Attribute, 1=Hold
Last State

8

Get/Set

Fault Value

BOOL

0=OFF, 1=ON

9

Get/Set

Idle Action

BOOL

0=Idle Value Attribute, 1=Hold Last
State

10

Get/Set

Idle Value

BOOL

0=OFF, 1=ON

113

Get/Set

Pr Fault Action

BOOL

0=Pr Fault Value Attribute,
1=Ignore

114

Get/Set

Pr Fault Value

BOOL

0=OFF, 1=ON

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

This manual is related to the following products: