L3 power factor, Total power factor, L3 power factor total power factor – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 253
![background image](/manuals/577641/253/background.png)
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
253
Metering and Diagnostics Chapter 7
Table 282 - L2 Power Factor (Parameter 77)
L3 Power Factor
L3 Power Factor (Parameter 78) reports the power factor for line 3 in percentage.
When Voltage Mode (Parameter 352) is set to any
Delta base setting, L3 Power
Factor is set to 0. When Single or Three Phase (Parameter 176) is set to
Single
Phase, L3 power factor is set to 0.
Table 283 - L3 Power Factor (Parameter 78)
Total Power Factor
Total Power Factor (Parameter 79) reports the total power factor of the
monitored power conductors in percentage. When Single or Three Phase
(Parameter 176) is set to
Three Phase, Total Power Factor is calculated as follows:
Total Power Factor = (L1 Power Factor + L2 Power Factor + L3 Power Factor) / 3
When Single or Three Phase (Parameter 176) is set to
Single Phase, Total Power
Factor is calculated as follows:
Total Power Factor = (L1 Power Factor + L2 Power Factor) / 2
Table 284 - Total Power Factor (Parameter 79)
Default Value
0.0
Minimum Value
-100.0
Maximum Value
100.0
Parameter Type
INT
Size (Bytes)
2
Scaling Factor
10
Units
%
Default Value
0.0
Minimum Value
-100.0
Maximum Value
100.0
Parameter Type
INT
Size (Bytes)
2
Scaling Factor
10
Units
%
Default Value
0.0
Minimum Value
-100.0
Maximum Value
100.0
Parameter Type
INT
Size (Bytes)
2
Scaling Factor
10