beautypg.com

Test mode trip – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 206

background image

206

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 5 Protective Trip and Warning Functions

The E300 Electronic Overload Relay will trip with a hardware fault trip
indication if:

No trip currently exists

Non-Volatile Storage Fault Trip is enabled

An issue exists in the E300 Electronic Overload Relay’s non-volatile
storage

If the E300 Electronic Overload Relay trips on a non-volatile storage fault trip,
the following will occur:

The TRIP/WARN LED will flash a red 3-long / 14-short blink pattern

Bit 13 in Control Trip Status (Parameter 7) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Test Mode Trip

Some motor control center enclosures include a Test Position in which the motor
power is disconnected from the enclosure, but the control power is still active.
This allows motor control center commissioning staff to verify that the motor
starter is mechanically working and communications are established with the
automation control system. The E300 Electronic Overload Relay provides the

IMPORTANT

The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:

Output PT00 Protection Fault Action (Parameter 304)

Output PT00 Protection Fault Value (Parameter 305)

Output PT01 Protection Fault Action (Parameter 310)

Output PT01 Protection Fault Value (Parameter 311)

Output PT02 Protection Fault Action (Parameter 316)

Output PT02 Protection Fault Value (Parameter 317)

Output Digital Module 1 Protection Fault Action (Parameter 322)

Output Digital Module 1 Protection Fault Value (Parameter 323)

Output Digital Module 2 Protection Fault Action (Parameter 328)

Output Digital Module 2 Protection Fault Value (Parameter 329)

Output Digital Module 3 Protection Fault Action (Parameter 334)

Output Digital Module 3 Protection Fault Value (Parameter 335)

Output Digital Module 4 Protection Fault Action (Parameter 340)

Output Digital Module 4 Protection Fault Value (Parameter 342)

This manual is related to the following products: