Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 5 Protective Trip and Warning Functions

Table 82 - Jam Trip Delay (Parameter 252)

Jam Trip Level

Jam Trip Level (Parameter 253) allows the installer to define the current at which
the E300 Electronic Overload Relay will trip on a jam. It is user-adjustable from
50…600% of the FLA Setting (Parameter 171).

Table 83 - Jam Trip Level (Parameter 253)

Jam Warning

The E300 Electronic Overload Relay will indicate a Jam warning if:

No warning currently exists

Jam Warning is enabled

Current is present

Jam Inhibit Time has expired

The maximum phase current is equal to or greater than the Jam Warning
Level

When the Jam Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 5-short blink pattern

Bit 4 in Current Warning Status (Parameter 10) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Default Value

5.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Default Value

250

Minimum Value

50

Maximum Value

600

Parameter Type

UINT

Size (Bytes)

2

Scaling Factor

1

Units

%FLA

IMPORTANT

The Jam Inhibitor timer starts after the maximum phase of load current
transitions from 0 A to 30% of the device’s minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for a jam condition until
the Jam Inhibit Time expires.