Chapter 5 Protective Trip and Warning Functions
Table 82 - Jam Trip Delay (Parameter 252)
Jam Trip Level
Jam Trip Level (Parameter 253) allows the installer to define the current at which
the E300 Electronic Overload Relay will trip on a jam. It is user-adjustable from
50…600% of the FLA Setting (Parameter 171).
Table 83 - Jam Trip Level (Parameter 253)
Jam Warning
The E300 Electronic Overload Relay will indicate a Jam warning if:
•
No warning currently exists
•
Jam Warning is enabled
•
Current is present
•
Jam Inhibit Time has expired
•
The maximum phase current is equal to or greater than the Jam Warning
Level
When the Jam Warning conditions are satisfied, the:
•
TRIP/WARN LED will flash a yellow 5-short blink pattern
•
Bit 4 in Current Warning Status (Parameter 10) will set to 1
•
Bit 1 in Device Status 0 (Parameter 20) will set to 1
•
Any relay outputs configured as a Warning Alarm will close
Default Value
5.0
Minimum Value
0.1
Maximum Value
25.0
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
10
Units
Sec
Default Value
250
Minimum Value
50
Maximum Value
600
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
1
Units
%FLA
IMPORTANT
The Jam Inhibitor timer starts after the maximum phase of load current
transitions from 0 A to 30% of the device’s minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for a jam condition until
the Jam Inhibit Time expires.