Protective Trip and Warning Functions Chapter 5

Under kVAR Generated Trip

The E300 Electronic Overload Relay will trip with an Under kVAR Generated
indication if:

No trip currently exists

Under kVAR Generated Trip is enabled

Current is present

Voltage is present

Under kVAR Generated Inhibit Time has expired

The total reactive power (kVAR) generated is less than the Under

kVAR Generated Trip Level for a time period greater than the Under
kVAR Generated Trip Delay.

If the E300 Electronic Overload Relay trips on an under reactive power (kVAR)
generated, the:

TRIP/WARN LED status indicator will flash a red 2-long / 5-short blink
pattern

Bit 4 in Power Trip Status (Parameter 6) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

IMPORTANT

The Over kVAR Consumed Warning function does not include a time delay
feature. Once the Over kVAR Consumed Inhibit Time has expired, the Over kVAR
Consumed Warning indication is instantaneous.