Chapter 5 Protective Trip and Warning Functions

TRIP/WARN LED will flash a yellow 1-long / 6-short blink pattern

Bit 5 in Voltage Warning Status (Parameter 11) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Over Frequency Warn Level

Over Frequency Warn Level (Parameter 376) allows the user to define the
frequency at which the E300 Electronic Overload Relay will indicate a warning.
It is user-adjustable from 46…65 Hz.

Table 142 - Over Frequency Warn Level (Parameter 376)

Power Based Protection

The E300 Electronic Overload Relay has the option to digitally monitor the
power supplied to an electric motor to protect against poor power quality or alert
users when power consumed by the motor is different from what is expected.
This protection is useful for pump cavitation and pump material change
detection. The following E300 Sensing Modules provide power monitoring
capabilities.

Table 143 - Power Capabilities

This power information is used for the following protective trip and warning
functions:

Under Real Power (kW) Trip/Warning

Over Real Power (kW) Trip/Warning

Under Reactive Power (kVAR) Trip/Warning

Over Real Power (kVAR) Trip/Warning

Default Value

62

Minimum Value

46

Maximum Value

65

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Hz

IMPORTANT

The Over Frequency Warning function does not include a time delay feature.
Once the Over Frequency Inhibit Time has expired, the Over Frequency Warning
indication is instantaneous.

Catalog Number

Measurement Method

L-L Voltage Trip/Warning Range

193-ESM-VIG-__-__

Internal

20-800V

592-ESM-VIG-__-__

Internal

20-800V

193-ESM-VIG-30A-CT

External

20-6500V