Analog output point object — class code 0x000b – Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 397
![background image](/manuals/577641/397/background.png)
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
397
EtherNet/IP Information Appendix C
The following common services are implemented for the Analog Input Point
Object.
Table 394 - Analog Input Point Object Common Services
Analog Output Point Object — CLASS CODE 0x000B
Table 395 - Analog Output Point Object Class Attributes
4 Instances of the Analog Output Point Object are supported. The Value
Attribute can then be overwritten by DeviceLogix.
Table 396 - Analog Output Point Object Instances
All instances contains the following attributes.
Table 397 - Analog Output Point Object Instance Attributes
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2
2
Get
Max. Instance
UINT
1
Instance
Name
Description
1
OutAnMod1Ch00
Analog Expansion Module 1 Output Channel 0
2
OutAnMod2Ch00
Analog Expansion Module 2 Output Channel 0
3
OutAnMod3Ch00
Analog Expansion Module 3 Output Channel 0
4
OutAnMod4Ch00
Analog Expansion Module 4 Output Channel 0
Attribute ID Access Rule
Name
Data Type
Value
3
Get/Set
Value
INT
Default = 0
8
Get
Value Data Type
USINT
0=INT
9
Get/Set
Fault Action
USINT
0=Hold Last State
1=Low Limit
2=High Limit
3=Zero
10
Get/Set
Idle Action
USINT
0=Hold Last State
1=Low Limit
2=High Limit
3=Zero
129
Get/Set
Input Binding
STRUCT:
USINT
Array of USINT
Size of appendix I encoded path
Appendix I encoded path:
NULL path means attribute 3 drives the
output.
Otherwise, this is a path to a bit in the
Bit Table.
130
Get/Set
Force Enable
BOOL
0=Disable, 1=Enable
131
Get/Set
Force Value
INT
Default = 0