EtherNet/IP Information Appendix C

The following common services are implemented for the Analog Input Point
Object.

Table 394 - Analog Input Point Object Common Services

Analog Output Point Object — CLASS CODE 0x000B

Table 395 - Analog Output Point Object Class Attributes

4 Instances of the Analog Output Point Object are supported. The Value
Attribute can then be overwritten by DeviceLogix.

Table 396 - Analog Output Point Object Instances

All instances contains the following attributes.

Table 397 - Analog Output Point Object Instance Attributes

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

2

Get

Max. Instance

UINT

1

Instance

Name

Description

1

OutAnMod1Ch00

Analog Expansion Module 1 Output Channel 0

2

OutAnMod2Ch00

Analog Expansion Module 2 Output Channel 0

3

OutAnMod3Ch00

Analog Expansion Module 3 Output Channel 0

4

OutAnMod4Ch00

Analog Expansion Module 4 Output Channel 0

Attribute ID Access Rule

Name

Data Type

Value

3

Get/Set

Value

INT

Default = 0

8

Get

Value Data Type

USINT

0=INT

9

Get/Set

Fault Action

USINT

0=Hold Last State
1=Low Limit
2=High Limit
3=Zero

10

Get/Set

Idle Action

USINT

0=Hold Last State
1=Low Limit
2=High Limit
3=Zero

129

Get/Set

Input Binding

STRUCT:
USINT
Array of USINT

Size of appendix I encoded path
Appendix I encoded path:
NULL path means attribute 3 drives the
output.
Otherwise, this is a path to a bit in the
Bit Table.

130

Get/Set

Force Enable

BOOL

0=Disable, 1=Enable

131

Get/Set

Force Value

INT

Default = 0