Chapter 5 Protective Trip and Warning Functions

No trip currently exists

Under kVA Trip is enabled

Current is present

Voltage is present

Under kVA Inhibit Time has expired

The total apparent power (kVA) is less than the Under kVA Trip Level for
a time period greater than the Under kVA Trip Delay.

If the E300 Electronic Overload Relay trips on an under apparent power (kVA),
the:

TRIP/WARN LED status indicator will flash a red 2-long / 7-short blink
pattern

Bit 6 in Power Trip Status (Parameter 6) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Under kVA Trip Delay

Under kVA Trip Delay (Parameter 403) allows the installer to define the time
period an under apparent power (kVA) condition must be present before a trip
occurs. It is adjustable from 0.1…25.0 seconds.

IMPORTANT

The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:

Output PT00 Protection Fault Action (Parameter 304)

Output PT00 Protection Fault Value (Parameter 305)

Output PT01 Protection Fault Action (Parameter 310)

Output PT01 Protection Fault Value (Parameter 311)

Output PT02 Protection Fault Action (Parameter 316)

Output PT02 Protection Fault Value (Parameter 317)

Output Digital Module 1 Protection Fault Action (Parameter 322)

Output Digital Module 1 Protection Fault Value (Parameter 323)

Output Digital Module 2 Protection Fault Action (Parameter 328)

Output Digital Module 2 Protection Fault Value (Parameter 329)

Output Digital Module 3 Protection Fault Action (Parameter 334)

Output Digital Module 3 Protection Fault Value (Parameter 335)

Output Digital Module 4 Protection Fault Action (Parameter 340)

Output Digital Module 4 Protection Fault Value (Parameter 342)