Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 352
352
Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Current Setup
continued
279
L2OCTripDelay
L2 Over Current Trip Delay
USINT
1
10
0
250
10
Sec
280
L2OCTripLevel
L2 Over Current Trip Level
USINT
1
1
10
200
100
%
281
L2OCWarningLevel
L2 Over Current Warning Level
USINT
1
1
10
200
90
%
282
L3OCTripDelay
L3 Over Current Trip Delay
USINT
1
10
0
250
10
Sec
283
L3OCTripLevel
L3 Over Current Trip Level
USINT
1
1
10
200
100
%
284
L3OCWarningLevel
L3 Over Current Warning Level
USINT
1
1
10
200
90
%
285
LineLossInhTime
Line Loss Inhibit Time
USINT
1
1
0
250
10
Sec
286
L1LossTripDelay
L1 Line Loss Trip Delay
USINT
1
10
0
250
10
Sec
287
L2LossTripDelay
L2 Line Loss Trip Delay
USINT
1
10
0
250
10
Sec
288
L3LossTripDelay
L3 Line Loss Trip Delay
USINT
1
10
0
250
10
Sec
Communications
Setup
289
OutputAssembly
Output Assembly Instance used
by IO Connections
UINT
2
1
0
180
144
290
InputAssembly
Input Assembly Instance used by
IO Connections
UINT
2
1
0
300
300
291
Datalink0
Produced I/O Assembly Datalink0
Parameter Number
UINT
2
1
0
560
0
292
Datalink1
Produced I/O Assembly Datalink1
Parameter Number
UINT
2
1
0
560
0
293
Datalink2
Produced I/O Assembly Datalink2
Parameter Number
UINT
2
1
0
560
0
294
Datalink3
Produced I/O Assembly Datalink3
Parameter Number
UINT
2
1
0
560
0
295
Datalink4
Produced I/O Assembly Datalink4
Parameter Number
UINT
2
1
0
560
0
296
Datalink5
Produced I/O Assembly Datalink5
Parameter Number
UINT
2
1
0
560
0
297
Datalink6
Produced I/O Assembly Datalink6
Parameter Number
UINT
2
1
0
560
0
298
Datalink7
Produced I/O Assembly Datalink7
Parameter Number
UINT
2
1
0
560
0
299
Reserved
300
Reserved
301
Reserved
302
Reserved
303
Reserved
Output Setup
304
OutPt00PrFltAct
Output Pt00 action on protection
fault
BOOL
1
1
0= GoToPrFltValue
1= IgnoreIfPossible
0
305
OutPt00PrFltVal
Output Pt00 value on protection
fault
BOOL
1
1
0=Open
1=Closed
0
306
OutPt00ComFltAct
Output Pt00 action on comms
fault
BOOL
1
1
0= GoToCommFltValue
1= HoldLastState
0
307
OutPt00ComFltVal
Out Pt00 value on comms fault
BOOL
1
1
0=Open
1=Closed
0
308
OutPt00ComIdlAct
Output Pt00 action on comms
idle
BOOL
1
1
0= GoToCommIdlValue
1= HoldLastState
0
309
OutPt00ComIdlVal
Output Pt00 value on comms idle BOOL
1
1
0=Open
1=Closed
0
310
OutPt01PrFltAct
Output Pt01 action on protection
fault
BOOL
1
1
0= GoToPrFltValue
1= IgnoreIfPossible
0
311
OutPt01PrFltVal
Output Pt01 value on protection
fault
BOOL
1
1
0=Open
1=Closed
0
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units