Chapter 4 Operating Modes
Figure 39 - Wiring Diagram
Timing Diagram
Figure 40 - Timing Diagram
Monitor (Custom)
The E300 Electronic Overload Relay’s Monitor (Custom) Operating Mode
allows the user to use the E300 Electronic Overload Relay as a monitoring device.
No configuration rules apply in this operating mode if the motor protection
features are disabled.
Rules
1.
If any protection trips are enabled (excluding Configuration, NVS, and
Hardware Fault trip), then set any of the Output Ptxx Assignments
(Parameters 202…204) to the appropriate value of Trip Relay, Control
Relay, Monitor Lx Trip Relay, or Monitor Lx Control Relay.
Wiring Diagram
Not Applicable
Timing Diagram
Not Applicable
Relay 1
Relay 0
Configured as a
Trip Relay
R13
R14
A1
A2
M
R03
R04
1
1
Contact shown with supply voltage applied.
Trip Relay
Trip Reset
Device
Status0.Trip
Present