Chapter 4 Operating Modes

Figure 39 - Wiring Diagram

Timing Diagram

Figure 40 - Timing Diagram

Monitor (Custom)

The E300 Electronic Overload Relay’s Monitor (Custom) Operating Mode
allows the user to use the E300 Electronic Overload Relay as a monitoring device.
No configuration rules apply in this operating mode if the motor protection
features are disabled.

Rules

1.

If any protection trips are enabled (excluding Configuration, NVS, and
Hardware Fault trip), then set any of the Output Ptxx Assignments
(Parameters 202…204) to the appropriate value of Trip Relay, Control
Relay, Monitor Lx Trip Relay, or Monitor Lx Control Relay.

Wiring Diagram

Not Applicable

Timing Diagram

Not Applicable

Relay 1

Relay 0

Configured as a

Trip Relay

R13

R14

A1

A2

M

R03

R04

1

1

Contact shown with supply voltage applied.

Trip Relay

Trip Reset

Device

Status0.Trip

Present