Appendix C EtherNet/IP Information
Comm Adapter Info Object — CLASS CODE 0x0C8
No class attributes are supported.
One Instance of the Comm Adapter Info Object is supported with the following
attributes
Table 432 - Comm Adapter Info Object Instance Attributes
The following common services are implemented
Table 433 - Comm Adapter Info Object Common Services
E300 Status Object — CLASS CODE 0x0375
The following instance attributes are supported:
Table 434 - E300 Status Object Instance Attributes
Attribute ID Access Rule
Name
Data Type
Value
1
Get
System Name String
String
Describes the E300 System components
installed
2
Get
Trip Status Parameter
Location
UINT
The parameter number of the first trip status
parameter
3
Get
Number of Trip Status
Params
UINT
The number of trip status parameters
following the parameter number given in
attribute 2. (Max=10)
4
Get
Warning Status
Parameter Location
UINT
The parameter number of the first warning
status parameter
5
Get
Number of
WarningStatus Params
UINT
The number of warning status parameters
following the param number given in
attribute 4. (Max=10)
6
Set
Selected Input
Assembly
UINT
The ENIP writes the input assembly instance
specified in an Ethernet/IP Forward Open
service connection point.
7
Get
Input Assembly Size
UINT
The size of the chosen Input Assembly
8
Set
Selected Output
Assembly
UINT
The ENIP writes the output assembly instance
specified in an Ethernet/IP Forward Open
service connection point.
9
Get
Input Assembly Size
UINT
The size of the chosen Output Assembly
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Attribute
Name
Byte
Data
2
Overload Data
0
OL Time to Trip
1
2
OL Time to Reset
3
4
%Therm Utilized
5