beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 190

background image

190

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 5 Protective Trip and Warning Functions

Table 191 -

Under Power Factor Leading Trip Level (Parameter 420)

Under Power Factor Leading Warning

The E300 Electronic Overload Relay will indicate an Under Power Factor
Leading warning if:

No warning currently exists

Under Power Factor Leading Warning is enabled

Current is present

Voltage is present

Under Power Factor Leading Inhibit Time has expired

The total power factor leading is equal to or less than the Under Power
Factor Leading Warning Level

When the Under Power Factor Leading Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 2-long / 11-short blink pattern

Bit 10 in Power Warning Status (Parameter 12) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Under Power Factor Leading Warn Level

Under Power Factor Leading Warn Level (Parameter 421) allows the user to
define the power factor leading at which the E300 Electronic Overload Relay will
indicate a warning. It is user-adjustable from 0…2,000,000 kW.

Default Value

90

Minimum Value

100

Maximum Value

0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%

IMPORTANT

The Under Power Factor Leading Inhibit Time starts after a phase voltage
transitions from 0V to 20V L-L and a phase of load current transitions from 0A
to 30% of the device’s minimum FLA setting. The E300 Electronic Overload
Relay does not begin monitoring for an under power factor leading condition
until the Under Power Factor Leading Inhibit Time expires.

This manual is related to the following products: