beautypg.com

Total apparent power, L1 power factor, L2 power factor power – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 252

background image

252

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 7 Metering and Diagnostics

Total Apparent Power

Total Apparent Power (Parameter 75) reports the total apparent power of the
monitored power conductors in kVA or MVA depending on the configuration
value for Power Scale (Parameter 377). When Single or Three Phase (Parameter
176) is set to

Three Phase, Total Apparent Power is calculated as follows:

Total Apparent Power = (L1 Apparent Power + L2 Apparent Power + L3
Apparent Power)

When Single or Three Phase (Parameter 176) is set to

Single Phase, Total

Apparent Power is calculated as follows:

Total Apparent Power = (L1 Apparent Power + L2 Apparent Power)

Table 280 - Total Apparent Power (Parameter 75)

L1 Power Factor

L1 Power Factor (Parameter 76) reports the power factor for line 1 in percentage.
When Voltage Mode (Parameter 352) is set to any

Delta base setting, L1 Power

Factor is set to 0.

Table 281 - L1 Power Factor (Parameter 76)

L2 Power Factor Power

L2 Power Factor (Parameter 77) reports the power factor for line 2 in percentage.
When Voltage Mode (Parameter 352) is set to any

Delta base setting, L2 Power

Factor is set to 0.

Default Value

0.000

Minimum Value

0.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kVA or MVA

Default Value

0.0

Minimum Value

-100.0

Maximum Value

100.0

Parameter Type

INT

Size (Bytes)

2

Scaling Factor

10

Units

%

This manual is related to the following products: