Chapter 5 Protective Trip and Warning Functions

Table 94 - L1 Under Current Trip Delay (Parameter 266)

L1 Under Current Trip Level

L1 Under Current Trip Level (Parameter 267) allows the installer to define the
current at which the E300 Electronic Overload Relay will trip on a L1 Under
Current. It is user-adjustable from 10…100% of the FLA Setting (Parameter
171).

Table 95 - L1 Under Current Trip Level (Parameter 267)

L1 Under Current Warning

The E300 Electronic Overload Relay will indicate an L1 Under Current warning
if:

No warning currently exists

L1 Under Current Warning is enabled

Current is present

The Under Current Inhibit Timer has expired

L1 Percent FLA (Parameter 47) is less than the L1 Under Current
Warning Level

Default Value

1.0

Minimum Value

0.1

Maximum Value

25.0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

10

Units

Sec

Default Value

35

Minimum Value

10

Maximum Value

100

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%FLA

IMPORTANT

The Under Current Inhibit Timer starts after the maximum phase of load
current transitions from 0A to 30% of the device’s minimum FLA setting. The
E300 Electronic Overload Relay does not begin monitoring for an under current
condition until the Under Current Inhibit Time expires.

IMPORTANT

For any given application, the practical limit of the L1 Under Current Trip Level
(Parameter 267), will be dependent on the FLA Setting and the lower limit of
the E300 Electronic Overload Relay’s current measurement capability