Chapter 5 Protective Trip and Warning Functions

Underload Trip

The E300 Electronic Overload Relay will trip with an underload indication if:

No trip currently exists

Underload Trip is enabled

Current is present

Underload Inhibit Time has expired

Minimum phase current is less than the Underload Trip Level for a time
period greater than the Underload Trip Delay.

If the E300 Electronic Overload Relay trips on an underload, the:

TRIP/WARN LED status indicator will flash a red 6-short blink pattern

Bit 5 in Current Trip Status (Parameter 4) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Underload Trip Delay

Underload Trip Delay (Parameter 256) allows the installer to define the time
period an underload condition must be present before a trip occurs. It is
adjustable from 0.1…25.0 s.

IMPORTANT

The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:

Output PT00 Protection Fault Action (Parameter 304)

Output PT00 Protection Fault Value (Parameter 305)

Output PT01 Protection Fault Action (Parameter 310)

Output PT01 Protection Fault Value (Parameter 311)

Output PT02 Protection Fault Action (Parameter 316)

Output PT02 Protection Fault Value (Parameter 317)

Output Digital Module 1 Protection Fault Action (Parameter 322)

Output Digital Module 1 Protection Fault Value (Parameter 323)

Output Digital Module 2 Protection Fault Action (Parameter 328)

Output Digital Module 2 Protection Fault Value (Parameter 329)

Output Digital Module 3 Protection Fault Action (Parameter 334)

Output Digital Module 3 Protection Fault Value (Parameter 335)

Output Digital Module 4 Protection Fault Action (Parameter 340)

Output Digital Module 4 Protection Fault Value (Parameter 342)