L1 reactive power, L2 reactive power – Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 249

background image

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

249

Metering and Diagnostics Chapter 7

Table 272 - Total Real Power (Parameter 67)

L1 Reactive Power

L1 Reactive Power (Parameter 68) reports the reactive power for line 1 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any

Delta base setting, L1

Reactive Power is set to 0.

Table 273 - L1 Reactive Power (Parameter 68)

L2 Reactive Power

L2 Reactive Power (Parameter 69) reports the reactive power for line 2 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any

Delta base setting, L2

Reactive Power is set to 0.

Table 274 - L2 Reactive Power (Parameter 69)

Default Value

0.000

Minimum Value

-2000000.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kW or MW

Default Value

0.000

Minimum Value

-2000000.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kVAR or MVAR

Default Value

0.000

Minimum Value

-2000000.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kVAR or MVAR