Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 185
![background image](/manuals/577641/185/background.png)
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
185
Protective Trip and Warning Functions Chapter 5
Table 186 - Under Power Factor Lagging Warn Level (Parameter 413)
Over Power Factor Lagging Trip
The E300 Electronic Overload Relay will trip with an Over Power Factor
Lagging indication if:
•
No trip currently exists
•
Over Power Factor Lagging Trip is enabled
•
Current is present
•
Voltage is present
•
Over Power Factor Lagging Inhibit Time has expired
•
The total power factor lagging is greater than the Over Power Factor
Lagging Trip Level for a time period greater than the Over Power Factor
Lagging Trip Delay.
If the E300 Electronic Overload Relay trips on an over power factor lagging, the:
•
TRIP/WARN LED status indicator will flash a red 2-long / 10-short
blink pattern
•
Bit 9 in Power Trip Status (Parameter 6) will set to 1
•
Bit 0 in Device Status 0 (Parameter 20) will set to 1
•
Any relay outputs configured as a Trip Relay will open
•
Any relay outputs configured as a Control Relay will open
•
Any relay outputs configured as a Trip Alarm will close
•
Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)
Default Value
-95
Minimum Value
-100
Maximum Value
0
Parameter Type
SINT
Size (Bytes)
1
Scaling Factor
1
Units
%
IMPORTANT
The Under Power Factor Lagging Warning function does not include a time
delay feature. Once the Under Power Factor Lagging Inhibit Time has expired,
the Under Power Factor Lagging Warning indication is instantaneous.