Protective Trip and Warning Functions Chapter 5

Table 186 - Under Power Factor Lagging Warn Level (Parameter 413)

Over Power Factor Lagging Trip

The E300 Electronic Overload Relay will trip with an Over Power Factor
Lagging indication if:

No trip currently exists

Over Power Factor Lagging Trip is enabled

Current is present

Voltage is present

Over Power Factor Lagging Inhibit Time has expired

The total power factor lagging is greater than the Over Power Factor
Lagging Trip Level for a time period greater than the Over Power Factor
Lagging Trip Delay.

If the E300 Electronic Overload Relay trips on an over power factor lagging, the:

TRIP/WARN LED status indicator will flash a red 2-long / 10-short
blink pattern

Bit 9 in Power Trip Status (Parameter 6) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Default Value

-95

Minimum Value

-100

Maximum Value

0

Parameter Type

SINT

Size (Bytes)

1

Scaling Factor

1

Units

%

IMPORTANT

The Under Power Factor Lagging Warning function does not include a time
delay feature. Once the Under Power Factor Lagging Inhibit Time has expired,
the Under Power Factor Lagging Warning indication is instantaneous.