beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 193

background image

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

193

Protective Trip and Warning Functions Chapter 5

Table 194 - Over Power Factor Leading Trip Level (Parameter 424)

Over Power Factor Leading Warning

The E300 Electronic Overload Relay will indicate an Over kVAR warning if:

No warning currently exists

Over Power Factor Leading Warning is enabled

Current is present

Voltage is present

Over Power Factor Leading Inhibit Time has expired

The total power factor leading is equal to or greater than the Over Power
Factor Leading Warning Level

When the Over Power Factor Leading Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 2-long / 12-short blink pattern

Bit 11 in Power Warning Status (Parameter 12) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

Over Power Factor Leading Warn Level

Over Power Factor Leading Warn Level (Parameter 425) allows the user to define
the power factor leading at which the E300 Electronic Overload Relay will
indicate a warning. It is user-adjustable from 0…2,000,000 kW.

Table 195 - Over Power Factor Leading Warn Level (Parameter 425)

Default Value

95

Minimum Value

100

Maximum Value

0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%

IMPORTANT

The Over Power Factor Leading Inhibit Time starts after a phase voltage
transitions from 0V to 20V L-L and a phase of load current transitions from 0A
to 30% of the device’s minimum FLA setting. The E300 Electronic Overload
Relay does not begin monitoring for an over power factor leading condition
until the Over Power Factor Leading Inhibit Time expires.

Default Value

90

Minimum Value

100

Maximum Value

0

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

%

This manual is related to the following products: