Parameter List Appendix B
Device Setup
(continued)
186
TripEnableC
Bitmask used to enable/disable
control based trips
UINT
2
1
Bit0= TestTrip
Bit1= PTCTrip
Bit2= DLXTrip
Bit3= OperStationTrip
Bit4= RemoteTrip
Bit5= BlockedStartTrip
Bit6= HardwareFltTrip
Bit7= ConfigTrip
Bit8= OptionMatchTrip
Bit9= DLXFBTimeoutTrip
Bit10= ExpansionBusTrip
Bit11= Reserved
Bit12= Reserved
Bit13= NVSTrip
Bit14=TestModeTrip
1
187
TripEnableA
Bitmask used to enable/disable
analog based trips
UINT
2
1
Bit0= InAnMod1Ch00Trip
Bit1= InAnMod1Ch01Trip
Bit2= InAnMod1Ch02Trip
Bit3= InAnMod2Ch00Trip
Bit4= InAnMod2Ch01Trip
Bit5= InAnMod2Ch02Trip
Bit6= InAnMod3Ch00Trip
Bit7= InAnMod3Ch01Trip
Bit8= InAnMod3Ch02Trip
Bit9= InAnMod4Ch00Trip
Bit10= InAnMod4Ch01Trip
Bit11= InAnMod4Ch02Trip
0
188
Reserved
189
WarningEnableI
Bitmask used to enable/disable
current based warnings
UINT
2
1
Bit0= OverloadWarning
Bit1= Reserved
Bit2= GroundFltWarning
Bit3= Reserved
Bit4= JamWarning
Bit5= UnderloadWarning
Bit6= CurrentImbalWarn
Bit7= L1UnderCurrWarn
Bit8= L2UnderCurrWarn
Bit9= L3UnderCurrWarn
Bit10= L1OverCurrenWarn
Bit11= L2OverCurrenWarn
Bit12= L3OverCurrenWarn
Bit13= L1LineLossWarn
Bit14= L2LineLossWarn
Bit15= L3LineLossWarn
0
190
WarningEnableV
Bitmask used to enable/disable
voltage based warnings
UINT
2
1
Bit0= UnderVoltageWarn
Bit1= OvervoltageWarn
Bit2= VoltageUnbalWarn
Bit3= PhaseRotationWrn
Bit4= UnderFreqWarning
Bit5= OverFreqWarning
0
Group
Param
No.
Parameter Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units