Chapter 5 Protective Trip and Warning Functions

Table 168 - Under kVAR Generated Warn Level (Parameter 397)

Over kVAR Generated Trip

The E300 Electronic Overload Relay will trip with an Over kVAR Generated
indication if:

No trip currently exists

Over kVAR Generated Trip is enabled

Current is present

Voltage is present

Over kVAR Generated Inhibit Time has expired

The total reactive power (kVAR) generated is greater than the Over

kVAR Generated Trip Level for a time period greater than the Over kVAR
Generated Trip Delay.

If the E300 Electronic Overload Relay trips on an over reactive power (kVAR)
generated, the:

TRIP/WARN LED status indicator will flash a red 2-long / 6-short blink
pattern

Bit 5 in Power Trip Status (Parameter 6) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

Default Value

0.000

Minimum Value

0.000

Maximum Value

2000000.000

Parameter Type

DINT

Size (Bytes)

4

Scaling Factor

1000

Units

kVAR

IMPORTANT

The Under kVAR Generated Warning function does not include a time delay
feature. Once the Under kVAR generated Inhibit Time has expired, the Under
kVAR Generated Warning indication is instantaneous.