Chapter 5 Protective Trip and Warning Functions
Table 168 - Under kVAR Generated Warn Level (Parameter 397)
Over kVAR Generated Trip
The E300 Electronic Overload Relay will trip with an Over kVAR Generated
indication if:
•
No trip currently exists
•
Over kVAR Generated Trip is enabled
•
Current is present
•
Voltage is present
•
Over kVAR Generated Inhibit Time has expired
•
The total reactive power (kVAR) generated is greater than the Over
•
kVAR Generated Trip Level for a time period greater than the Over kVAR
Generated Trip Delay.
If the E300 Electronic Overload Relay trips on an over reactive power (kVAR)
generated, the:
•
TRIP/WARN LED status indicator will flash a red 2-long / 6-short blink
pattern
•
Bit 5 in Power Trip Status (Parameter 6) will set to 1
•
Bit 0 in Device Status 0 (Parameter 20) will set to 1
•
Any relay outputs configured as a Trip Relay will open
•
Any relay outputs configured as a Control Relay will open
•
Any relay outputs configured as a Trip Alarm will close
•
Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)
Default Value
0.000
Minimum Value
0.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVAR
IMPORTANT
The Under kVAR Generated Warning function does not include a time delay
feature. Once the Under kVAR generated Inhibit Time has expired, the Under
kVAR Generated Warning indication is instantaneous.