Chapter 5 Protective Trip and Warning Functions

L2 Line Loss Warning is enabled

L2 Line Loss is activated via the appropriately programmed digital input
(see Input Assignments, Parameters 196-201, in Chapter 3)

Line Loss Inhibit Timer has expired

L2 Percent FLA (Parameter 48) is equal to 0%

When the L2 Line Loss Warning conditions are satisfied, the:

TRIP/WARN LED will flash a yellow 15-short blink pattern

Bit 14 in Current Warning Status (Parameter 10) will set to 1

Bit 1 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Warning Alarm will close

L3 Line Loss Trip

The E300 Electronic Overload Relay will trip with a L3 Line Loss indication if:

No trip currently exists

L3 Over Current Trip is enabled

L3 Line Loss is activated via the appropriately programmed digital input
(see Input Assignments, Parameters 196-201, in Chapter 3)

Line Loss Inhibit Timer has expired

L3 Percent FLA (Parameter 49) is equal to 0% for a time period greater
than the L3 Line Loss Trip Delay.

If the E300 Electronic Overload Relay trips on a L3 Line Loss, the:

TRIP/WARN LED status indicator will flash a red 16-short blink pattern

Bit 15 in Current Trip Status (Parameter 4) will set to 1

Bit 0 in Device Status 0 (Parameter 20) will set to 1

Any relay outputs configured as a Trip Relay will open

Any relay outputs configured as a Control Relay will open

Any relay outputs configured as a Trip Alarm will close

Any relay outputs configured as a Normal Relay will be placed in their
Protection Fault state (if so programmed)

IMPORTANT

The L2 Line Loss Warning function does not include a time delay feature. Once
the Line Loss Inhibit Timer has expired, the L2 Line Loss Warning indication is
instantaneous.