Chapter 5 Protective Trip and Warning Functions

Reactive Power (kVAR) Protection

The E300 Electronic Overload Relay has the capability to protect against reactive
power (kVAR) for specific applications that require the monitoring of both
voltage and current. The user can protect or issue a warning in the event that the
reactive power (kVAR) of an electric motor is either too high or too low.

Under kVAR Consumed Inhibit Time

Under kVAR Consumed Inhibit Time (Parameter 386) allows the installer to
inhibit an under reactive power (kVAR) consumed trip and warning from
occurring during the motor starting sequence. It is adjustable from 0…250
seconds.

Table 156 - Under kVAR Consumed Inhibit Time (Parameter 386)

Over kVAR Consumed Inhibit Time

Over kVAR Consumed Inhibit Time (Parameter 390) allows the installer to
inhibit an over reactive power (kVAR) consumed trip and warning from
occurring during the motor starting sequence. It is adjustable from 0…250
seconds.

Table 157 - Over kVAR Consumed Inhibit Time (Parameter 390)

IMPORTANT

The Over kW Warning function does not include a time delay feature. Once the
Over kW Inhibit Time has expired, the Over kW Warning indication is
instantaneous.

Default Value

10

Minimum Value

0

Maximum Value

250

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Sec

Default Value

10

Minimum Value

0

Maximum Value

250

Parameter Type

USINT

Size (Bytes)

1

Scaling Factor

1

Units

Sec