beautypg.com

Rockwell Automation 592- E300 Overload Relay User Manual User Manual

Page 78

background image

78

Rockwell Automation Publication 193-UM015B-EN-P - June 2014

Chapter 5 Protective Trip and Warning Functions

Current Trip Enable (Parameter 183) and Current Warning Enable (Parameter
189) are used to enable the respective current based protective trip and warning
functions.

Table 54 - Current Trip Enable (Parameter 183)

Table 55 - Current Warning Enable (Parameter 189)

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Function

X

Overload Trip

X

Phase Loss Trip

X

Ground Fault Trip

X

Stall Trip

X

Jam Trip

X

Underload Trip

X

Current Imbalance Trip

X

L1 Under Current Trip

X

L2 Under Current Trip

X

L3 Under Current Trip

X

L1 Over Current Trip

X

L2 Over Current Trip

X

L3 Over Current Trip

X

L1 Line Loss Trip

X

L2 Line Loss Trip

X

L3 Line Loss Trip

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Function

X

Overload Warning

Reserved

X

Ground Fault Warning

Reserved

X

Jam Warning

X

Underload Warning

X

Current Imbalance Warning

X

L1 Under Current Warning

X

L2 Under Current Warning

X

L3 Under Current Warning

X

L1 Over Current Warning

X

L2 Over Current Warning

X

L3 Over Current Warning

X

L1 Line Loss Warning

X

L2 Line Loss Warning

X

L3 Line Loss Warning

This manual is related to the following products: