Rockwell Automation 592- E300 Overload Relay User Manual User Manual
Page 78
![background image](/manuals/577641/78/background.png)
78
Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Current Trip Enable (Parameter 183) and Current Warning Enable (Parameter
189) are used to enable the respective current based protective trip and warning
functions.
Table 54 - Current Trip Enable (Parameter 183)
Table 55 - Current Warning Enable (Parameter 189)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Overload Trip
X
Phase Loss Trip
X
Ground Fault Trip
X
Stall Trip
X
Jam Trip
X
Underload Trip
X
Current Imbalance Trip
X
L1 Under Current Trip
X
L2 Under Current Trip
X
L3 Under Current Trip
X
L1 Over Current Trip
X
L2 Over Current Trip
X
L3 Over Current Trip
X
L1 Line Loss Trip
X
L2 Line Loss Trip
X
L3 Line Loss Trip
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
X
Overload Warning
Reserved
X
Ground Fault Warning
Reserved
X
Jam Warning
X
Underload Warning
X
Current Imbalance Warning
X
L1 Under Current Warning
X
L2 Under Current Warning
X
L3 Under Current Warning
X
L1 Over Current Warning
X
L2 Over Current Warning
X
L3 Over Current Warning
X
L1 Line Loss Warning
X
L2 Line Loss Warning
X
L3 Line Loss Warning